WOODWARD 8200-226

 

Part Nr: Woodward 8200-226

Brand:   Type:
State:  

Buy at DCS-Centers.com, Best price and Big Stock.

Woodward 8200-226 SPC Servo Position Controller Technical Specifications

 
Item Specification
Part Number 8200-226
Product Full Name SPC Servo Position Controller
Reference Manual Woodward Manual 26236 Rev N
Main Application Closed-loop position control for turbine & engine actuators/valves
Nominal Supply Voltage 24 V DC
Operating Voltage Range 18 V DC ~ 32 V DC
Max Continuous Input Current 1.1 A
Typical Power Dissipation 20 W
Peak Inrush Current Max 20 A (100 ms)
Recommended External Fuse 5 A, 125 V
Power Circuit Protection Reverse polarity, overvoltage & short-circuit protection
Supported Demand Input Signals 4–20 mA, 1–5 V DC, PWM
4–20mA Input Impedance 200 Ω
Signal Fault Trigger Threshold <1 mA or >23 mA
Compatible Position Feedback LVDT, RVDT, DC position transducers
Control Resolution 11-bit full scale
Linear Accuracy (25°C) 0.2% Full Scale
Temperature Drift 300 ppm/°C
Configurable Actuator Drive Current ±10 / ±25 / ±50 / ±100 / ±250 mA
Built-in Dither Function 0–10% adjustable amplitude, 25 Hz, 25% duty cycle
Output Filter Lag Time 6 ms
Position Retransmission Output 4–20 mA, 12-bit resolution
Fieldbus Communication DeviceNet
Service Debug Port 9-pin RS232 D-Sub connector
Configuration Software SPC Service Tool (Windows PC)
Overall Dimensions (W×H×D) 329 mm × 203 mm × 65 mm
Net Weight 1.55 kg
Protection Class IP20 (cabinet mount only)
Operating Temperature -40 °C ~ +70 °C
Storage & Transport Temperature -40 °C ~ +70 °C
Relative Humidity 5%–95% RH, non-condensing
Vibration Resistance 0.7 g, 5–2000 Hz
Shock Resistance 30 g, 11 ms half-sine pulse
Main Certifications CE, CSA, Marine, ATEX
ATEX Explosion Standard ATEX II 3 G Ex nA IIC T6 Gc
EMC Standard Heavy-duty industrial electromagnetic immunity
Core Control Functions Closed-loop position regulation, anti-hunting gain, integral stabilization
Diagnostic Alarms Wire break, short circuit, actuator fault, power supply monitoring
Typical Industries Power generation, oil & gas, marine prime mover control

parts photo album​

Woodward 8200-226

Click edit button to change this text. Lorem ipsum dolor sit amet consectetur adipiscing elit dolor
Hot Sell

Click edit button to change this text. Lorem ipsum dolor sit amet, consectetur adipiscing elit. Ut elit tellus, luctus nec ullamcorper mattis, pulvinar dapibus leo.

Customer feedback
Rated 9 out of 10

People who viewed this item also viewed

Made in Germany

Click edit button to change this text. Lorem ipsum dolor sit amet consectetur adipiscing elit dolor

Woodward 8200-226

Welcome to send your RFQ

Please provide your detailed information below, we will contact you within 24 hours and arrange for a business manager to provide you with a quotation