Sales02@aotewell.com

Tel: +86-133-6088-1849

WhatsApp / Wechat / Mobile

1503VCBMC5

 

Part Nr: Allen Bradley 1503VC-BMC5 /E IntelliVAC Vacuum Contactor Control 1503VCBMC5

Brand:   Type:
State:  

Buy at DCS-Centers.com, Best price and Big Stock.

Allen Bradley 1503VC-BMC5 /E IntelliVAC Vacuum Contactor Control 1503VCBMC5

Allen‑Bradley 1503VC‑BMC5 Ser.E IntelliVAC Contactor Control Module Parameter Table

Basic Information

Item Specification
Part Number 1503VC‑BMC5
Series IntelliVAC
Series Revision SER.E
Manufacturer Rockwell Automation / Allen‑Bradley
Origin Made in Canada
Certification CE, cRUus Listed

Rated Supply Voltages

Power Type Range Frequency Note
AC Input 110…240 V RMS 50–60 Hz
DC Input 110…250 V DC

Supply Current

Current Item Rating Remark
Idle Current Max 125 mA Normal standby state
Inrush Peak Current 25 A peak No external capacitor required
Sealed Capacitor Current Max 1.0 A Internal capacitor circuit

External Capacitor Terminals

Pin No. Definition
1 Negative (-)
2 Positive (+)

Contactor Interface Terminal Definition

Pin No. Function Description
3 Coil 2 COM Common for trip coil (mechanical latch)
4 Coil 2 Trip coil terminal
5 Coil 1 COM Common for close coil
6 Coil 1 Close coil terminal
7 Open Command + Positive open command input
8 Open Command – Negative open command input
9 Close Command + Positive close command input
10 Close Command – Negative close command input

Command Voltage Range

  • DC Command: 50 V … 250 V DC
  • AC Command: 100 V … 240 V AC

Terminal Note

Command signal assignments will change under DeviceNet control or multi‑contactor mode; refer to official user manual.

Auxiliary Contact Terminals

Pin No. Function Restriction
11 Auxiliary Contact Do not feed external power to these pins
12 Auxiliary Contact Do not feed external power to these pins

Contactor & Module Status Outputs

Pin No. Signal Electrical Load Capacity
13 / 14 Module Status 250 V AC, 5 A resistive load

30 V DC, 5 A resistive load

15 / 16 Contactor Status 250 V AC, 5 A resistive load

30 V DC, 5 A resistive load

Other Specifications

  1. Configuration: DIP switch parameter settings printed on inner side of module cover
  2. Warning Marking
    • DANGER label: Hazardous voltage exists inside; de‑energize power before removing cover, cover must stay installed during operation
    • CAUTION label: Module pre‑configured at factory; verify all settings before energizing, improper configuration will damage equipment, remove this label to access power terminals
  3. Mechanical Structure: DIN rail wall mount metal housing, top terminal plug connector, dedicated Module Status indicator window
  4. Internal Mark: T14 internal production marking, serial number label affixed on side housing

parts photo album​

Allen Bradley 1503VC-BMC5 /E IntelliVAC Vacuum Contactor Control 1503VCBMC5

Click edit button to change this text. Lorem ipsum dolor sit amet consectetur adipiscing elit dolor
Hot Sell

Click edit button to change this text. Lorem ipsum dolor sit amet, consectetur adipiscing elit. Ut elit tellus, luctus nec ullamcorper mattis, pulvinar dapibus leo.

Customer feedback
Rated 9 out of 10

People who viewed this item also viewed

Made in Germany

Click edit button to change this text. Lorem ipsum dolor sit amet consectetur adipiscing elit dolor

Allen Bradley 1503VC-BMC5 /E IntelliVAC Vacuum Contactor Control 1503VCBMC5

Welcome to send your RFQ

Please provide your detailed information below, we will contact you within 24 hours and arrange for a business manager to provide you with a quotation