Full Technical Data (English)
表格
| Parameter | Value |
|---|---|
| Order No. | 6SE7036-1EE85-1AA0 |
| Product Type | Regenerative feedback unit / Active infeed unit |
| Voltage Class | 380–480 V 3-phase AC |
| Frame Size | E |
| Protection Class | IP00 (open chassis) |
| Cooling | Forced-air cooling |
Input (Mains) Data
表格
| Parameter | Value |
|---|---|
| Input Voltage | 3 AC 380 V … 480 V |
| Frequency | 50 / 60 Hz |
| Rated Input Current | 361 A |
| Rated Apparent Power | 250 kVA |
| Rated Active Power | 250 kW |
DC Link Output Data
表格
| Parameter | Value |
|---|---|
| Nominal DC Link Voltage | 540 V DC (at 400 V AC) |
| DC Voltage Range | 510 V … 680 V DC |
| Rated DC Current | 361 A |
| Overload | 110% for 60 s every 10 min
150% for 3 s |
| Power Factor | ≥ 0.95 (at rated load) |
| Efficiency | ≥ 98 % |
Control & Auxiliary
表格
| Parameter | Value |
|---|---|
| Control Supply Voltage | 24 V DC ±10% |
| Auxiliary Power Consumption | ≤ 100 W |
| Communication | PROFIBUS-DP, RS485 |
| Control Modes | Voltage control, current limiting, regenerative operation |
Environmental & Mechanical
表格
| Parameter | Value |
|---|---|
| Ambient Temperature | 0 … +40 °C (derate above) |
| Storage Temperature | -25 … +70 °C |
| Humidity | 5% – 95% non-condensing |
| Altitude | Up to 1000 m (derate above) |
| Dimensions (W×H×D) | approx. 450 × 880 × 420 mm |
| Weight | approx. 165 kg |