Main |
Range of Product |
Altivar Process ATV600 |
Product or Component Type |
Variable speed drive |
Product Specific Application |
Process and utilities |
Device short name |
ATV630 |
Variant |
Standard version |
Product destination |
Asynchronous motors |
Synchronous motors |
EMC filter |
Integrated 164.04 ft (50 m) IEC 61800-3 category C2 |
Integrated 492.1 ft (150 m) IEC 61800-3 category C3 |
IP degree of protection |
IP21IEC 61800-5-1 |
IP21IEC 60529 |
[Us] rated supply voltage |
380…480 V |
Degree of protection |
UL type 1 UL 508C |
Type of cooling |
Forced convection |
Supply frequency |
50…60 Hz – 5…5 % |
[Us] rated supply voltage |
380…480 V – 15…10 % |
Motor power kW |
1.5 kW normal duty) |
0.75 kW heavy duty) |
Maximum Horse Power Rating |
2 hp normal duty |
1 hp heavy duty |
Line current |
3 A 380 V normal duty) |
2.6 A 480 V normal duty) |
1.7 A 380 V heavy duty) |
1.5 A 480 V heavy duty) |
Prospective line Isc |
50 kA |
Apparent power |
2.2 kVA 480 V normal duty) |
1.2 kVA 480 V heavy duty) |
Continuous output current |
4 A 4 kHz normal duty |
2.2 A 4 kHz heavy duty |
Asynchronous motor control profile |
Variable torque standard |
Constant torque standard |
Optimized torque mode |
Synchronous motor control profile |
Permanent magnet motor |
Synchronous reluctance motor |
Speed drive output frequency |
0.1…500 Hz |
Nominal switching frequency |
4 kHz |
Switching frequency |
2…12 kHz adjustable |
4…12 kHz with derating factor |
Safety function |
STO (safe torque off) SIL 3 |
Discrete input logic |
16 preset speeds |
Communication Port Protocol |
Modbus TCP |
Ethernet |
Modbus serial |
Option card |
Slot A communication module, Profibus DP V1 |
Slot A communication module, PROFINET |
Slot A communication module, DeviceNet |
Slot A communication module, Modbus TCP/EtherNet/IP |
Slot A communication module, CANopen daisy chain RJ45 |
Slot A communication module, CANopen SUB-D 9 |
Slot A communication module, CANopen screw terminals |
Slot A/slot B digital and analog I/O extension module |
Slot A/slot B output relay extension module |
Slot A communication module, Ethernet IP/Modbus TCP/MD-Link |
communication module, BACnet MS/TP |
communication module, Ethernet Powerlink |
Complementary |
Mounting Mode |
Wall mount |
Maximum transient current |
4.4 A 60 s normal duty) |
3.3 A 60 s heavy duty) |
Phase |
3 phase |
Discrete output number |
0 |
Discrete output type |
Relay outputs R1A, R1B, R1C 250 V AC 3000 mA |
Relay outputs R1A, R1B, R1C 30 V DC 3000 mA |
Relay outputs R2A, R2C 250 V AC 5000 mA |
Relay outputs R2A, R2C 30 V DC 5000 mA |
Relay outputs R3A, R3C 250 V AC 5000 mA |
Relay outputs R3A, R3C 30 V DC 5000 mA |
Output voltage |
<= power supply voltage |
Permissible temporary current boost |
1.1 x In 60 s normal duty) |
1.5 x In 60 s heavy duty) |
Motor slip compensation |
Can be suppressed |
Adjustable |
Not available in permanent magnet motor law |
Automatic whatever the load |
Acceleration and deceleration ramps |
Linear adjustable separately from 0.01…9999 s |
Physical interface |
Ethernet |
2-wire RS 485 |
Braking to standstill |
By DC injection |
Protection type |
Thermal protection motor |
Safe torque off motor |
Motor phase break motor |
Thermal protection drive |
Safe torque off drive |
Overheating drive |
Overcurrent between output phases and earth drive |
Overload of output voltage drive |
Short-circuit protection drive |
Motor phase break drive |
Overvoltages on the DC bus drive |
Line supply overvoltage drive |
Line supply undervoltage drive |
Line supply phase loss drive |
Overspeed drive |
Break on the control circuit drive |
Transmission Rate |
10, 100 Mbits |
4800 bps, 9600 bps, 19200 bps, 38.4 Kbps |
Frequency resolution |
Display unit 0.1 Hz |
Analog input 0.012/50 Hz |
Transmission frame |
RTU |
Electrical connection |
Control removable screw terminals 0.5…1.5 mm² AWG 20…AWG 16 |
Motor screw terminal 2.5…6 mm² AWG 14…AWG 10 |
Line side screw terminal 2.5…6 mm² AWG 14…AWG 10 |
Connector type |
RJ45 on the remote graphic terminal)Ethernet/Modbus TCP |
RJ45 on the remote graphic terminal)Modbus serial |
Data format |
8 bits, configurable odd, even or no parity |
Type of polarization |
No impedance |
Exchange mode |
Half duplex, full duplex, autonegotiation Ethernet/Modbus TCP |
Number of addresses |
1…247 Modbus serial |
Method of access |
Slave Modbus TCP |
Supply |
External supply for digital inputs 24 V DC 19…30 V), <1.25 mA overload and short-circuit protection |
Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 mA overload and short-circuit protection |
Internal supply for digital inputs and STO 24 V DC 21…27 V), <200 mA overload and short-circuit protection |
Local signalling |
for local diagnostic 3 LEDs |
for embedded communication status 3 LEDs (dual colour) |
for communication module status 4 LEDs (dual colour) |
for presence of voltage 1 LED (red) |
Width |
5.7 in (144 mm) |
Height |
13.8 in (350 mm) |
Depth |
8.0 in (203 mm) |
Net Weight |
9.9 lb(US) (4.5 kg) |
Analogue input number |
3 |
Analogue input type |
AI1, AI2, AI3 software-configurable voltage 0…10 V DC 31.5 kOhm 12 bits |
AI1, AI2, AI3 software-configurable current 0…20 mA 250 Ohm 12 bits |
AI2 voltage analog input – 10…10 V DC 31.5 kOhm 12 bits |
Discrete input number |
8 |
Discrete input type |
DI7, DI8 programmable as pulse input 0…30 kHz, 24 V DC <= 30 V) |
Input compatibility |
DI1…DI6 discrete input level 1 PLC IEC 61131-2 |
DI5, DI6 discrete input level 1 PLC IEC 65A-68 |
STOA, STOB discrete input level 1 PLC IEC 61131-2 |
Discrete input logic |
Positive logic (source) DI1…DI8), < 5 V, > 11 V |
Negative logic (sink) DI1…DI8), > 16 V, < 10 V |
Analogue output number |
2 |
Analogue output type |
Software-configurable voltage AQ1, AQ2 0…10 V DC 470 Ohm 10 bits |
Software-configurable current AQ1, AQ2 0…20 mA 10 bits |
Software-configurable current DQ-, DQ+ 30 V DC |
Software-configurable current DQ-, DQ+ 100 mA |
Sampling duration |
2 ms +/- 0.5 ms DI1…DI4) – discrete input |
5 ms +/- 1 ms DI5, DI6) – discrete input |
5 ms +/- 0.1 ms AI1, AI2, AI3) – analog input |
10 ms +/- 1 ms AO1) – analog output |
Accuracy |
+/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input |
+/- 1 % AO1, AO2 for a temperature variation 60 °C analog output |
Linearity error |
AI1, AI2, AI3 +/- 0.15 % of maximum value analog input |
AO1, AO2 +/- 0.2 % analog output |
Relay output number |
3 |
Relay output type |
Configurable relay logic R1 fault relay NO/NC 100000 cycles |
Configurable relay logic R2 sequence relay NO 100000 cycles |
Configurable relay logic R3 sequence relay NO 100000 cycles |
Refresh time |
Relay output R1, R2, R3)5 ms +/- 0.5 ms) |
Minimum switching current |
Relay output R1, R2, R3 5 mA 24 V DC |
Maximum switching current |
Relay output R1, R2, R3 resistive, cos phi = 1 3 A 250 V AC |
Relay output R1, R2, R3 resistive, cos phi = 1 3 A 30 V DC |
Relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 250 V AC |
Relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 30 V DC |
Isolation |
Between power and control terminals |
Maximum output frequency |
500 kHz |
Maximum Input Current per Phase |
3.0 A |
Variable speed drive application selection |
Building – HVAC compressor centrifugal |
Food and beverage processing other application |
Mining mineral and metal fan |
Mining mineral and metal pump |
Oil and gas fan |
Water and waste water other application |
Building – HVAC screw compressor |
Food and beverage processing pump |
Food and beverage processing fan |
Food and beverage processing atomization |
Oil and gas electro submersible pump (ESP) |
Oil and gas water injection pump |
Oil and gas jet fuel pump |
Oil and gas compressor for refinery |
Water and waste water centrifuge pump |
Water and waste water positive displacement pump |
Water and waste water electro submersible pump (ESP) |
Water and waste water screw pump |
Water and waste water lobe compressor |
Water and waste water screw compressor |
Water and waste water compressor centrifugal |
Water and waste water fan |
Water and waste water conveyor |
Water and waste water mixer |
Motor power range AC-3 |
1.1…2 kW 380…440 V 3 phase |
1.1…2 kW 480…500 V 3 phase |
Quantity per Set |
1 |
enclosure mounting |
Wall mounted |
Environment |
Insulation resistance |
> 1 MOhm 500 V DC for 1 minute to earth |
Noise level |
54.5 dB 86/188/EEC |
Power dissipation in W |
Natural convection 28 W 380 V 4 kHz |
Forced convection 41 W 380 V 4 kHz |
Volume of cooling air |
10038.7 Gal/hr(US) (38 m3/h) |
Operating position |
Vertical +/- 10 degree |
Maximum THDI |
<48 % full load IEC 61000-3-12 |
Electromagnetic compatibility |
Electrostatic discharge immunity test level 3 IEC 61000-4-2 |
Radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3 |
Electrical fast transient/burst immunity test level 4 IEC 61000-4-4 |
1.2/50 µs – 8/20 µs surge immunity test level 3 IEC 61000-4-5 |
Conducted radio-frequency immunity test level 3 IEC 61000-4-6 |
Pollution degree |
2 IEC 61800-5-1 |
Vibration resistance |
1.5 mm peak to peak 2…13 Hz)IEC 60068-2-6 |
1 gn 13…200 Hz)IEC 60068-2-6 |
Shock resistance |
15 gn 11 ms IEC 60068-2-27 |
Relative humidity |
5…95 % without condensation IEC 60068-2-3 |
Ambient air temperature for operation |
5…122 °F (-15…50 °C) without derating) |
122…140 °F (50…60 °C) with derating factor) |
Ambient Air Temperature for Storage |
-40…158 °F (-40…70 °C) |
Operating altitude |
<= 3280.84 ft (1000 m) without derating |
1000…4800 m with current derating 1 % per 100 m |
Product Certifications |
ATEX INERIS |
DNV-GL |
ATEX zone 2/22 |
UL |
CSA |
TÜV |
marking |
CE |
Standards |
UL 508C |
IEC 61800-3 |
IEC 61800-3 environment 1 category C2 |
EN/IEC 61800-3 environment 2 category C3 |
IEC 61800-5-1 |
IEC 61000-3-12 |
IEC 60721-3 |
IEC 61508 |
IEC 13849-1 |
Overvoltage category |
III |
Regulation loop |
Adjustable PID regulator |
Noise level |
54.5 dB |
Pollution degree |
2 |
Ordering and shipping details |
Category |
US1CP4E22205 |
Discount Schedule |
CP4E |
GTIN |
3606480758102 |
Returnability |
Yes |
Country of origin |
ID |