SPEED DRIVE,100HP,460V,ATV61
ATV61HD75N4
Main | |
Range of Product | Altivar 61 |
Product or Component Type | Variable speed drive |
Product Specific Application | Pumping and ventilation machine |
Component name | ATV61 |
Motor power kW | 75 kW, 3 phase 380…480 V |
Maximum Horse Power Rating | 100 hp, 3 phase 380…480 V |
power supply voltage | 380…480 V – 15…10 % |
supply number of phases | 3 phase |
Line current | 137 A 480 V 3 phase 75 kW / 100 hp |
167 A 380 V 3 phase 75 kW / 100 hp | |
EMC filter | Level 3 EMC filter |
Assembly style | With heat sink |
Apparent power | 109.9 kVA 380 V 3 phase 75 kW / 100 hp |
maximum prospective line Isc | 22 kA 3 phase |
Maximum transient current | 192 A 60 s, 3 phase |
Nominal switching frequency | 12 kHz |
Switching frequency | 1…16 kHz adjustable |
12…16 kHz with derating factor | |
asynchronous motor control | Voltage/frequency ratio – Energy Saving, quadratic U/f |
Voltage/frequency ratio, 5 points | |
Flux vector control without sensor, standard | |
Voltage/frequency ratio, 2 points | |
Synchronous motor control profile | Vector control without sensor, standard |
Communication Port Protocol | CANopen |
Modbus | |
Type of polarization | No impedance Modbus |
Option card | Communication card APOGEE FLN |
Communication card BACnet | |
Communication card CC-Link | |
Controller inside programmable card | |
Communication card DeviceNet | |
Communication card EtherNet/IP | |
Communication card Fipio | |
I/O extension card | |
Communication card Interbus-S | |
Communication card LonWorks | |
Communication card METASYS N2 | |
Communication card Modbus Plus | |
Communication card Modbus TCP | |
Communication card Modbus/Uni-Telway | |
Multi-pump card | |
Communication card Profibus DP | |
Communication card Profibus DP V1 | |
Complementary | |
Product destination | Asynchronous motors |
Synchronous motors | |
power supply voltage limits | 323…528 V |
power supply frequency | 50…60 Hz – 5…5 % |
power supply frequency limits | 47.5…63 Hz |
Continuous output current | 124 A 12 kHz, 460 V – 3 phase |
160 A 12 kHz, 380 V – 3 phase | |
Output frequency | 0.1…500 Hz |
Speed range | 1…100 in open-loop mode, without speed feedback |
Speed accuracy | +/- 10 % of nominal slip 0.2 Tn to Tn without speed feedback |
Torque accuracy | +/- 15 % in open-loop mode, without speed feedback |
Transient overtorque | 130 % of nominal motor torque +/- 10 % 60 s |
Braking torque | <= 125 % with braking resistor |
30 % without braking resistor | |
Regulation loop | Frequency PI regulator |
Motor slip compensation | Adjustable |
Not available in voltage/frequency ratio (2 or 5 points) | |
Can be suppressed | |
Automatic whatever the load | |
diagnostic | for drive voltage 1 LED (red) |
Output voltage | <= power supply voltage |
electrical isolation | Between power and control terminals |
type of cable for mounting in an enclosure | With an IP21 or an IP31 kit 3 IEC cable 104 °F (40 °C), copper 70 °C / PVC |
With UL Type 1 kit 3 UL 508 cable 104 °F (40 °C), copper 75 °C / PVC | |
Without mounting kit 1 IEC cable 113 °F (45 °C), copper 70 °C / PVC | |
Without mounting kit 1 IEC cable 113 °F (45 °C), copper 90 °C / XLPE/EPR | |
Electrical connection | Terminal 2.5 mm² / AWG 14 AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1…LI6, PWR) |
Terminal 150 mm² / 300 kcmil L1/R, L2/S, L3/T, U/T1, V/T2, W/T3, PC/-, PO, PA/+, PA, PB) | |
Tightening torque | 5.3 lbf.in (0.6 N.m) AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1…LI6, PWR) |
362.9 lbf.in (41 N.m), 360 lb.in L1/R, L2/S, L3/T, U/T1, V/T2, W/T3, PC/-, PO, PA/+, PA, PB) | |
Supply | Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC, +/- 5 %, <10 mA overload and short-circuit protection |
Internal supply 24 V DC 21…27 V), <200 mA overload and short-circuit protection | |
External supply 24 V DC 19…30 V) | |
Analogue input number | 2 |
Analogue input type | AI1-/Al1+ bipolar differential voltage +/- 10 V DC 24 V max 11 bits + sign |
AI2 software-configurable current 0…20 mA 242 Ohm 11 bits | |
AI2 software-configurable voltage 0…10 V DC 24 V max 30000 Ohm 11 bits | |
sampling time | 2 ms +/- 0.5 ms AI1-/Al1+) – analog input |
2 ms +/- 0.5 ms Al2) – analog input | |
2 ms +/- 0.5 ms AO1) – analog output | |
2 ms +/- 0.5 ms LI1…LI5) – discrete input | |
2 ms +/- 0.5 ms LI6)if configured as logic input – discrete input | |
absolute accuracy precision | +/- 0.6 % AI1-/Al1+) for a temperature variation 60 °C |
+/- 0.6 % AI2) for a temperature variation 60 °C | |
+/- 1 % AO1) for a temperature variation 60 °C | |
Linearity error | +/- 0.15 % of maximum value AI1-/Al1+) |
+/- 0.15 % of maximum value AI2) | |
+/- 0.2 % AO1) | |
Analogue output number | 1 |
Analogue output type | AO1 software-configurable current 0…20 mA 500 Ohm 10 bits |
AO1 software-configurable voltage 0…10 V DC 470 Ohm 10 bits | |
AO1 software-configurable logic output 10 V, 20 mA | |
Discrete output number | 2 |
Discrete output type | Configurable relay logic R1A, R1B, R1C) NO/NC – 100000 cycles |
Configurable relay logic R2A, R2B) NO – 100000 cycles | |
maximum response time | <= 100 ms in STO (Safe Torque Off) |
R1A, R1B, R1C <= 7 ms +/- 0.5 ms | |
R2A, R2B <= 7 ms +/- 0.5 ms | |
Minimum switching current | 3 mA 24 V DC configurable relay logic |
Maximum switching current | R1, R2 2 A 250 V AC inductive, cos phi = 0.4 7 ms |
R1, R2 2 A 30 V DC inductive, cos phi = 0.4 7 ms | |
R1, R2 5 A 250 V AC resistive, cos phi = 1 0 ms | |
R1, R2 5 A 30 V DC resistive, cos phi = 1 0 ms | |
Discrete input number | 7 |
Discrete input type | Programmable LI1…LI5) 24 V DC <= 30 V)level 1 PLC – 3500 Ohm |
Switch-configurable LI6) 24 V DC <= 30 V)level 1 PLC – 3500 Ohm | |
Switch-configurable PTC probe LI6)0…6 – 1500 Ohm | |
Safety input PWR) 24 V DC <= 30 V) – 1500 Ohm | |
Discrete input logic | Negative logic (sink) LI1…LI5), > 16 V, < 10 V |
Positive logic (source) LI1…LI5), < 5 V, > 11 V | |
Negative logic (sink) LI6)if configured as logic input, > 16 V, < 10 V | |
Positive logic (source) LI6)if configured as logic input, < 5 V, > 11 V | |
Acceleration and deceleration ramps | Linear adjustable separately from 0.01 to 9000 s |
S, U or customized | |
Automatic adaptation of ramp if braking capacity exceeded, by using resistor | |
Braking to standstill | By DC injection |
Protection type | Against exceeding limit speed drive |
Against input phase loss drive | |
Break on the control circuit drive | |
Input phase breaks drive | |
Line supply overvoltage drive | |
Line supply undervoltage drive | |
Overcurrent between output phases and earth drive | |
Overheating protection drive | |
Overvoltages on the DC bus drive | |
Power removal drive | |
Short-circuit between motor phases drive | |
Thermal protection drive | |
Motor phase break motor | |
Power removal motor | |
Thermal protection motor | |
Insulation resistance | > 1 mOhm 500 V DC for 1 minute to earth |
Frequency resolution | Analog input 0.024/50 Hz |
Display unit 0.1 Hz | |
Connector type | 1 RJ45 on front face)Modbus |
1 RJ45 on terminal)Modbus | |
Male SUB-D 9 on RJ45CANopen | |
Physical interface | 2-wire RS 485 Modbus |
Transmission frame | RTU Modbus |
Transmission rate | 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps Modbus on terminal |
9600 bps, 19200 bps Modbus on front face | |
20 kbps, 50 kbps, 125 kbps, 250 kbps, 500 kbps, 1 Mbps CANopen | |
Data format | 8 bits, 1 stop, even parity Modbus on front face |
8 bits, odd even or no configurable parity Modbus on terminal | |
Number of addresses | 1…127 CANopen |
1…247 Modbus | |
Method of access | Slave CANopen |
Marking | CE |
Operating position | Vertical +/- 10 degree |
Net Weight | 97.003 lb(US) (44 kg) |
Width | 12.6 in (320 mm) |
Height | 24.8 in (630 mm) |
Depth | 11.4 in (290 mm) |
Environment | |
Noise level | 63.7 dB 86/188/EEC |
Dielectric strength | 3535 V DC between earth and power terminals |
5092 V DC between control and power terminals | |
Electromagnetic compatibility | Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 |
Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 | |
Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 | |
Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 | |
Voltage dips and interruptions immunity test conforming to IEC 61000-4-11 | |
Standards | IEC 60721-3-3 class 3S2 |
IEC 61800-3 environments 1 category C3 | |
IEC 61800-5-1 | |
UL Type 1 | |
EN 55011 class A group 2 | |
IEC 60721-3-3 class 3C1 | |
IEC 61800-3 environments 2 category C3 | |
IEC 61800-3 | |
Product Certifications | GOST |
CSA | |
C-tick | |
NOM 117 | |
UL | |
DNV | |
Pollution degree | 3 IEC 61800-5-1 |
3 UL 840 | |
degree of proctection | IP20 on upper part without blanking plate on cover IEC 60529 |
IP20 on upper part without blanking plate on cover IEC 61800-5-1 | |
IP21 IEC 60529 | |
IP21 IEC 61800-5-1 | |
IP41 on upper part IEC 60529 | |
IP41 on upper part IEC 61800-5-1 | |
IP54 on lower part IEC 60529 | |
IP54 on lower part IEC 61800-5-1 | |
Vibration resistance | 1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6 |
1.5 mm peak to peak (f= 3…13 Hz) conforming to IEC 60068-2-6 | |
Shock resistance | 15 gn 11 ms IEC 60068-2-27 |
Relative humidity | 5…95 % without condensation IEC 60068-2-3 |
5…95 % without dripping water IEC 60068-2-3 | |
Ambient air temperature for operation | 14…122 °F (-10…50 °C) (without derating) |
122…140 °F (50…60 °C) (with derating factor) | |
Ambient Air Temperature for Storage | -13…158 °F (-25…70 °C) |
Operating altitude | <= 3280.84 ft (1000 m) without derating |
3280.84…9842.52 ft (1000…3000 m) with current derating 1 % per 100 m | |
Ordering and shipping details | |
Category | 22138-ATV61 60 THRU 150 HP DRIVES |
Discount Schedule | CP4C |
GTIN | 00785901639626 |
Returnability | No |
Country of origin | IN |