Main |
Range of Product |
Altivar 12 |
Product or Component Type |
Variable speed drive |
Product Specific Application |
Simple machine |
Mounting Mode |
Cabinet mount |
Communication Port Protocol |
Modbus |
Supply frequency |
50/60 Hz +/- 5 % |
[Us] rated supply voltage |
200…240 V – 15…10 % |
Nominal output current |
10 A |
Maximum Horse Power Rating |
3 hp |
Motor power kW |
2.2 kW |
Maximum Horse Power Rating |
3 hp |
EMC filter |
Integrated |
IP degree of protection |
IP20 |
Complementary |
Discrete input number |
4 |
Discrete output number |
2 |
Analogue input number |
1 |
Analogue output number |
1 |
Relay output number |
1 |
Physical interface |
2-wire RS 485 |
Connector Type |
1 RJ45 |
Continuous output current |
10 A 4 kHz |
Method of access |
Server Modbus serial |
Speed drive output frequency |
0.5…400 Hz |
Speed range |
1…20 |
Sampling duration |
20 ms +/- 1 ms logic input |
10 ms analogue input |
Linearity error |
+/- 0.3 % of maximum value analogue input |
Frequency resolution |
Analog input converter A/D, 10 bits |
Display unit 0.1 Hz |
Time constant |
20 ms +/- 1 ms for reference change |
Transmission Rate |
9.6 kbit/s |
19.2 kbit/s |
38.4 kbit/s |
Transmission frame |
RTU |
Number of addresses |
1…247 |
Data format |
8 bits, configurable odd, even or no parity |
Communication service |
Read holding registers (03) 29 words |
Write single register (06) 29 words |
Write multiple registers (16) 27 words |
Read/write multiple registers (23) 4/4 words |
Read device identification (43) |
Type of polarization |
No impedance |
4 quadrant operation possible |
FALSE |
Asynchronous motor control profile |
Sensorless flux vector control |
Quadratic voltage/frequency ratio |
Voltage/frequency ratio (V/f) |
Maximum output frequency |
4 kHz |
Transient overtorque |
150…170 % of nominal motor torque depending on drive rating and type of motor |
Acceleration and deceleration ramps |
Linear from 0 to 999.9 s |
U |
S |
Motor slip compensation |
Adjustable |
Preset in factory |
Switching frequency |
2…16 kHz adjustable |
4…16 kHz with derating factor |
Nominal switching frequency |
4 kHz |
Braking to standstill |
By DC injection |
Brake chopper integrated |
FALSE |
Line current |
24.0 A 100 V heavy duty) |
20.2 A 120 V heavy duty) |
Maximum Input Current per Phase |
20.2 A |
Maximum output voltage |
240 V |
Apparent power |
4.8 kVA 240 V heavy duty) |
Maximum transient current |
15.0 A 60 s heavy duty) |
16.5 A 2 s heavy duty) |
Network Frequency |
50-60 Hz |
Relative symmetric network frequency tolerance |
5% |
Prospective line Isc |
1 kA |
Base load current at high overload |
10.0 A |
Power dissipation in W |
Forced cooling 93.0 W |
With safety function Safely Limited Speed (SLS) |
FALSE |
With safety function Safe brake management (SBC/SBT) |
FALSE |
With safety function Safe Operating Stop (SOS) |
FALSE |
With safety function Safe Position (SP) |
FALSE |
With safety function Safe programmable logic |
FALSE |
With safety function Safe Speed Monitor (SSM) |
FALSE |
With safety function Safe Stop 1 (SS1) |
FALSE |
With sft fct Safe Stop 2 (SS2) |
FALSE |
With safety function Safe torque off (STO) |
FALSE |
With safety function Safely Limited Position (SLP) |
FALSE |
With safety function Safe Direction (SDI) |
FALSE |
Protection type |
Line supply overvoltage |
Line supply undervoltage |
Overcurrent between output phases and earth |
Overheating protection |
Short-circuit between motor phases |
Against input phase loss in three-phase |
Thermal motor protection via the drive by continuous calculation of I²t |
Tightening torque |
10.6 lbf.in (1.2 N.m) |
Insulation |
Electrical between power and control |
Quantity per Set |
Set of 1 |
Width |
4.1 in (105 mm) |
Height |
5.6 in (142 mm) |
Depth |
6.1 in (156.2 mm) |
Product Weight |
3.09 lb(US) (1.4 kg) |
Environment |
Operating altitude |
> 3280.84…6561.68 ft (> 1000…2000 m) with current derating 1 % per 100 m |
<= 3280.84 ft (1000 m) without derating |
Operating position |
Vertical +/- 10 degree |
Product Certifications |
NOM |
CSA |
C-tick |
UL |
GOST |
RCM |
KC |
marking |
CE |
Standards |
UL 508C |
UL 618000-5-1 |
IEC 61800-5-1 |
IEC 61800-3 |
Assembly style |
With heat sink |
Electromagnetic compatibility |
Electrical fast transient/burst immunity test level 4 IEC 61000-4-4 |
Electrostatic discharge immunity test level 3 IEC 61000-4-2 |
Immunity to conducted disturbances level 3 IEC 61000-4-6 |
Radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3 |
Surge immunity test level 3 IEC 61000-4-5 |
Voltage dips and interruptions immunity test IEC 61000-4-11 |
Environmental class (during operation) |
Class 3C3 according to IEC 60721-3-3 |
Class 3S2 according to IEC 60721-3-3 |
Maximum acceleration under shock impact (during operation) |
150 m/s² at 11 ms |
Maximum acceleration under vibrational stress (during operation) |
10 m/s² at 13…200 Hz |
Maximum deflection under vibratory load (during operation) |
1.5 mm at 2…13 Hz |
Volume of cooling air |
4226.8 Gal/hr(US) (16 m3/h) |
Overvoltage category |
Class III |
Regulation loop |
Adjustable PID regulator |
Electromagnetic emission |
Radiated emissions environment 1 category C2 IEC 61800-3 2…16 kHz shielded motor cable |
Conducted emissions with integrated EMC filter environment 1 category C1 IEC 61800-3 2, 4, 8, 12 and 16 kHz shielded motor cable <16.4 ft (5 m) |
Conducted emissions with additional EMC filter environment 1 category C1 IEC 61800-3 4…12 kHz shielded motor cable <65.6 ft (20 m) |
Conducted emissions with additional EMC filter environment 1 category C2 IEC 61800-3 4…12 kHz shielded motor cable <164.04 ft (50 m) |
Conducted emissions with additional EMC filter environment 2 category C3 IEC 61800-3 4…12 kHz shielded motor cable <164.04 ft (50 m) |
Conducted emissions with integrated EMC filter environment 1 category C2 IEC 61800-3 4…16 kHz shielded motor cable <16.4 ft (5 m) |
Conducted emissions with integrated EMC filter environment 1 category C2 IEC 61800-3 2, 4, 8, 12 and 16 kHz shielded motor cable <32.8 ft (10 m) |
Vibration resistance |
1 gn 13…200 Hz)IEC 60068-2-6 |
1.5 mm peak to peak 3…13 Hz) – drive unmounted on symmetrical DIN rail – IEC 60068-2-6 |
Shock resistance |
15 gn 11 ms IEC 60068-2-27 |
Relative humidity |
5…95 % without condensation IEC 60068-2-3 |
5…95 % without dripping water IEC 60068-2-3 |
Noise level |
45 dB |
Pollution degree |
2 |
Ambient air transport temperature |
-13.0000000000…158.0000000000 °F (-25…70 °C) |
Ambient air temperature for operation |
14.0000000000…122.0000000000 °F (-10…50 °C) without derating |
122.0000000000…140.0000000000 °F (50…60 °C) with current derating 2.2 % per °C |
Ambient Air Temperature for Storage |
-13.0000000000…158.0000000000 °F (-25…70 °C) |
Ordering and shipping details |
Category |
US1CP4B22042 |
Discount Schedule |
CP4B |
GTIN |
3.60648E+12 |
Returnability |
Yes |
Country of origin |
US |