Main |
Range of product |
Altivar Process ATV600 |
Product or component type |
Variable speed drive |
Product specific application |
Process and utilities |
Device short name |
ATV650 |
variant |
With disconnect switch |
product destination |
Asynchronous motors |
Synchronous motors |
EMC filter |
Integrated with 50 m conforming to IEC 61800-3 category C2 |
Integrated with 150 m conforming to IEC 61800-3 category C3 |
IP degree of protection |
IP55 conforming to IEC 60529 |
IP55 conforming to IEC 61800-5-1 |
[Us] rated supply voltage |
380…480 V |
Type of cooling |
Forced convection |
Supply frequency |
50…60 Hz – 5…5 % |
[Us] rated supply voltage |
380…480 V – 15…10 % |
Motor power kW |
22 kW (heavy duty) |
30 kW (normal duty) |
Motor power hp |
30 hp heavy duty |
40 hp normal duty |
Line current |
45.9 A at 480 V (normal duty) |
40.5 A at 380 V (heavy duty) |
35.8 A at 480 V (heavy duty) |
53.3 A at 380 V (normal duty) |
Prospective line Isc |
50 kA |
Apparent power |
29.8 kVA at 480 V (heavy duty) |
38.2 kVA at 480 V (normal duty) |
Continuous output current |
59 A at 4 kHz for normal duty |
46.3 A at 4 kHz for heavy duty |
Asynchronous motor control profile |
Optimized torque mode |
Constant torque standard |
Variable torque standard |
Synchronous motor control profile |
Synchronous reluctance motor |
Permanent magnet motor |
Speed drive output frequency |
0.1…500 Hz |
Nominal switching frequency |
4 kHz |
Switching frequency |
4…12 kHz with derating factor |
2…12 kHz adjustable |
Safety function |
STO (safe torque off) SIL 3 |
Discrete input logic |
16 preset speeds |
Communication port protocol |
Ethernet |
Modbus serial |
Modbus serial |
Option card |
Slot A: communication module, PROFINET |
Slot A: communication module, DeviceNet |
Slot A: communication module, Modbus TCP/EtherNet/IP |
Slot A: communication module, CANopen daisy chain RJ45 |
Slot A: communication module, CANopen SUB-D 9 |
Slot A: communication module, CANopen screw terminals |
Slot A/slot B: digital and analog I/O extension module |
Slot A/slot B: output relay extension module |
Slot A: communication module, Ethernet IP/Modbus TCP/MD-Link |
Communication module, BACnet MS/TP |
Communication module, Ethernet Powerlink |
Slot A: communication module, Profibus DP V1 |
Complementary |
mounting mode |
Wall mount |
Maximum transient current |
69.5 A during 60 s (normal duty) |
67.7 A during 60 s (heavy duty) |
Network number of phases |
3 phases |
Discrete output number |
0 |
Discrete output type |
Relay outputs R1A, R1B, R1C 250 V AC 3000 mA |
Relay outputs R1A, R1B, R1C 30 V DC 3000 mA |
Relay outputs R2A, R2C 250 V AC 5000 mA |
Relay outputs R2A, R2C 30 V DC 5000 mA |
Relay outputs R3A, R3C 250 V AC 5000 mA |
Relay outputs R3A, R3C 30 V DC 5000 mA |
Output voltage |
<= power supply voltage |
Permissible temporary current boost |
1.5 x In during 60 s (heavy duty) |
1.1 x In during 60 s (normal duty) |
Motor slip compensation |
Automatic whatever the load |
Can be suppressed |
Not available in permanent magnet motor law |
Can be suppressed |
Acceleration and deceleration ramps |
Linear adjustable separately from 0.01…9999 s |
Physical interface |
Ethernet |
2-wire RS 485 |
Braking to standstill |
By DC injection |
Protection type |
Safe torque off: motor |
Motor phase break: motor |
Thermal protection: drive |
Safe torque off: drive |
Overheating: drive |
Overcurrent between output phases and earth: drive |
Overload of output voltage: drive |
Short-circuit protection: drive |
Motor phase break: drive |
Overvoltages on the DC bus: drive |
Line supply overvoltage: drive |
Line supply undervoltage: drive |
Line supply phase loss: drive |
Overspeed: drive |
Break on the control circuit: drive |
Thermal protection: motor |
Transmission rate |
10, 100 Mbits |
4800 bps, 9600 bps, 19200 bps, 38.4 Kbps |
Frequency resolution |
Analog input: 0.012/50 Hz |
Display unit: 0.1 Hz |
Transmission frame |
RTU |
Electrical connection |
Line side: screw terminal 25…50 mm²/AWG 4…AWG 1 |
Motor: screw terminal 25…50 mm²/AWG 4…AWG 1 |
Control: removable screw terminals 0.5…1.5 mm² |
Connector type |
RJ45 (on the remote graphic terminal) for Modbus serial |
RJ45 (on the remote graphic terminal) for Ethernet/Modbus TCP |
Data format |
8 bits, configurable odd, even or no parity |
Type of polarization |
No impedance |
Exchange mode |
Half duplex, full duplex, autonegotiation Ethernet/Modbus TCP |
Number of addresses |
1…247 for Modbus serial |
Method of access |
Slave Modbus TCP |
Supply |
Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection |
Internal supply for digital inputs and STO: 24 V DC (21…27 V), <200 mA, protection type: overload and short-circuit protection |
External supply for digital inputs: 24 V DC (19…30 V), <1.25 mA, protection type: overload and short-circuit protection |
Local signalling |
3 LEDs (dual colour) for embedded communication status |
4 LEDs (dual colour) for communication module status |
1 LED (red) for presence of voltage |
3 LEDs for local diagnostic |
Width |
290 mm |
Height |
910 mm |
Depth |
401 mm |
Net weight |
50 kg |
Analogue input number |
3 |
Analogue input type |
AI1, AI2, AI3 software-configurable voltage: 0…10 V DC, impedance: 31.5 kOhm, resolution 12 bits |
AI1, AI2, AI3 software-configurable current: 0…20 mA, impedance: 250 Ohm, resolution 12 bits |
AI2 voltage analog input: – 10…10 V DC, impedance: 31.5 kOhm, resolution 12 bits |
Discrete input number |
8 |
Discrete input type |
DI7, DI8 programmable as pulse input: 0…30 kHz, 24 V DC (<= 30 V) |
Input compatibility |
DI5, DI6: discrete input level 1 PLC conforming to IEC 65A-68 |
STOA, STOB: discrete input level 1 PLC conforming to IEC 61131-2 |
DI1…DI6: discrete input level 1 PLC conforming to IEC 61131-2 |
Discrete input logic |
Positive logic (source) (DI1…DI8), < 5 V (state 0), > 11 V (state 1) |
Negative logic (sink) (DI1…DI8), > 16 V (state 0), < 10 V (state 1) |
Analogue output number |
2 |
Analogue output type |
Software-configurable voltage AQ1, AQ2: 0…10 V DC impedance 470 Ohm, resolution 10 bits |
Software-configurable current AQ1, AQ2: 0…20 mA, resolution 10 bits |
Software-configurable current DQ-, DQ+: 30 V DC |
Software-configurable current DQ-, DQ+: 100 mA |
Sampling duration |
5 ms +/- 1 ms (DI5, DI6) – discrete input |
5 ms +/- 0.1 ms (AI1, AI2, AI3) – analog input |
10 ms +/- 1 ms (AO1) – analog output |
2 ms +/- 0.5 ms (DI1…DI4) – discrete input |
Accuracy |
+/- 1 % AO1, AO2 for a temperature variation 60 °C analog output |
+/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input |
Linearity error |
AO1, AO2: +/- 0.2 % for analog output |
AI1, AI2, AI3: +/- 0.15 % of maximum value for analog input |
Relay output number |
3 |
Relay output type |
Configurable relay logic R2: sequence relay NO electrical durability 100000 cycles |
Configurable relay logic R3: sequence relay NO electrical durability 100000 cycles |
Configurable relay logic R1: fault relay NO/NC electrical durability 100000 cycles |
Refresh time |
Relay output (R1, R2, R3): 5 ms (+/- 0.5 ms) |
Minimum switching current |
Relay output R1, R2, R3: 5 mA at 24 V DC |
Maximum switching current |
Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 30 V DC |
Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC |
Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC |
Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 250 V AC |
Isolation |
Between power and control terminals |
Maximum output frequency |
500 kHz |
Maximum input current |
53.3 A |
Variable speed drive application selection |
Food and beverage processing other application |
Mining mineral and metal fan |
Mining mineral and metal pump |
Oil and gas fan |
Water and waste water other application |
Building – HVAC screw compressor |
Food and beverage processing pump |
Food and beverage processing fan |
Food and beverage processing atomization |
Oil and gas electro submersible pump (ESP) |
Oil and gas water injection pump |
Oil and gas jet fuel pump |
Oil and gas compressor for refinery |
Water and waste water centrifuge pump |
Water and waste water positive displacement pump |
Water and waste water electro submersible pump (ESP) |
Water and waste water screw pump |
Water and waste water lobe compressor |
Water and waste water screw compressor |
Water and waste water compressor centrifugal |
Water and waste water fan |
Water and waste water conveyor |
Water and waste water mixer |
Motor power range AC-3 |
30…50 kW at 480…500 V 3 phases |
Quantity per set |
1 |
enclosure mounting |
Wall mounted |
Environment |
Insulation resistance |
> 1 MOhm 500 V DC for 1 minute to earth |
Noise level |
69.7 dB conforming to 86/188/EEC |
Operating position |
Vertical +/- 10 degree |
Maximum THDI |
<48 % from 80…100 % of load conforming to IEC 61000-3-12 |
Electromagnetic compatibility |
Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 |
Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 |
1.2/50 µs – 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 |
Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 |
Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 |
Pollution degree |
2 conforming to IEC 61800-5-1 |
Vibration resistance |
1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6 |
1.5 mm peak to peak (f= 2…13 Hz) conforming to IEC 60068-2-6 |
Shock resistance |
15 gn for 11 ms conforming to IEC 60068-2-27 |
Relative humidity |
5…95 % without condensation conforming to IEC 60068-2-3 |
Ambient air temperature for operation |
40…50 °C (with derating factor) |
-15…40 °C (without derating) |
ambient air temperature for storage |
-40…70 °C |
Operating altitude |
1000…4800 m with current derating 1 % per 100 m |
<= 1000 m without derating |
Product certifications |
TÜV |
DNV-GL |
UL |
ATEX zone 2/22 |
ATEX INERIS |
Marking |
CE |
Standards |
IEC 61800-3 |
IEC 61800-3 environment 1 category C2 |
EN/IEC 61800-3 environment 2 category C3 |
IEC 61800-5-1 |
IEC 61000-3-12 |
IEC 60721-3 |
IEC 61508 |
IEC 13849-1 |
Overvoltage category |
III |
Regulation loop |
Adjustable PID regulator |
Noise level |
69.7 dB |
Pollution degree |
3 |