6SL3220-1YD56-0CB0
SINAMICS G120XA Rated power 315kW 3AC 380V -20% to 440V +10% Integrated class A C3 filter 110% 60s per 600s without Operator Panel Integrated Fieldbus: MODBUS RTU, BACnet MS/TP, USS 6DI, 4DQ, 2AI, 2AQ, 1Mot_t Protection: IP20 Frame Size: FSH 1487.5x548x410 (HxWxD)
|
Category
|
Item
|
Parameter
|
|
Rated Data
|
Rated power IEC 400V (LO)
|
315.00 kW
|
|
Rated Data
|
Rated voltage
|
400 V
|
|
Rated Data
|
Line voltage
|
380 … 440 V +10 % -15 % (FSH size)
|
|
Rated Data
|
Line frequency
|
47 … 63 Hz ±5%
|
|
Rated Data
|
Input phases
|
3 AC
|
|
Rated Data
|
Output phases
|
3 AC
|
|
Rated Data
|
Rated current (LO)
|
590.00 A
|
|
Rated Data
|
Rated current 400V (IN)
|
617.00 A
|
|
Rated Data
|
Max. output current
|
649.00 A (110% of rated current)
|
|
Rated Data
|
Max. output current (overload)
|
110% of rated current for 60 s in a 600 s cycle time
|
|
Rated Data
|
Low Overload (LO)
|
110% base load current IL for 60 s in a 600 s cycle time
|
|
Rated Data
|
Pulse frequency
|
2 kHz
|
|
Rated Data
|
Output frequency for vector control
|
0 … 100 Hz
|
|
Rated Data
|
Output frequency for V/f control
|
0 … 100 Hz
|
|
General Technical Specifications
|
Efficiency η
|
0.98
|
|
General Technical Specifications
|
Power factor cos φ 1
|
0.99
|
|
General Technical Specifications
|
Power factor λ
|
0.75 … 0.93
|
|
General Technical Specifications
|
Power loss³)
|
6.750 kW (typical)
|
|
General Technical Specifications
|
EMC category (with accessories)
|
Category C3
|
|
General Technical Specifications
|
Filter class (integrated)
|
RFI suppression filter for Category C3 (integrated A-C3 class filter)
|
|
General Technical Specifications
|
Sound pressure level (1m)
|
72.5 dB (typical)
|
|
General Technical Specifications
|
Safety function “Safe Torque Off”
|
Without SIRIUS device (e.g. via S7-1500F)
|
|
General Technical Specifications
|
Ambient temperature
|
0 ℃ ~ 50 ℃, derating above 40 ℃ (FSH size)
|
|
General Technical Specifications
|
Altitude
|
0 ~ 4000 m, derating above 1000 m
|
|
General Technical Specifications
|
Cooling method
|
Forced air cooling
|
|
General Technical Specifications
|
Protection class
|
IP20
|
|
Inputs / Outputs
|
Standard digital inputs – Number
|
6
|
|
Inputs / Outputs
|
Standard digital inputs – Max. inrush current
|
15 mA
|
|
Inputs / Outputs
|
Standard digital inputs – Switching level: 0 → 1
|
11 V
|
|
Inputs / Outputs
|
Standard digital inputs – Switching level: 1 → 0
|
5 V
|
|
Inputs / Outputs
|
Fail-safe digital inputs – Number
|
0
|
|
Inputs / Outputs
|
Digital outputs – Number as relay changeover contact
|
4 (250V AC 1A / 30V DC 1A)
|
|
Inputs / Outputs
|
Digital outputs – Number as transistor
|
0
|
|
Inputs / Outputs
|
Digital outputs – Output (resistive load)
|
DC 30 V, 1.0 A
|
|
Inputs / Outputs
|
Analog / digital inputs – Number
|
2 (0~10 V; 0/4~20 mA, Differential input)
|
|
Inputs / Outputs
|
Analog / digital inputs – Resolution
|
12 bit
|
|
Inputs / Outputs
|
Analog / digital inputs – Switching threshold: 0 → 1
|
4 V
|
|
Inputs / Outputs
|
Analog / digital inputs – Switching threshold: 1 → 0
|
1.6 V
|
|
Inputs / Outputs
|
Analog outputs – Number
|
2 (0~10 V; 0/4~20 mA, Non-isolated output)
|
|
Inputs / Outputs
|
PTC / KTY interface – Motor temperature sensor input
|
1, sensors that can be connected: PTC, KTY, PT1000 and Thermo-Click, accuracy ±5 ℃
|
|
Closed-loop Control Techniques
|
V/f linear / square-law / parameterizable
|
Yes
|